D6 Labs
™
Engineered IoT Solutions
Wh
sker
o
TM
www.d6labs.com
Page 1
sales@d6labs.com
© Copyright 2026 Digital Six Laboratories, All Right Reserved
1-844-365-8647
WB1-9-xx-DCA4NNNN-0000-xx
Whisker.Block
®
, Dry Contact & 4-20 mA Analog Input
D6 Labs Whisker-Block_3qtr-View_01
General Description
A long-range, 900 MHz, wireless sensor in a durable, transulcent
IP67 case with LED feedback, including two external input channels
for connecting a dry contact sensor and a 420 mA analog sensor. The
sensors are prewired to an included wire bundle, which connects to
the Whisker.Block
®
via an M8 connector. Also included is an internal,
on-board, thermistor with +/- 1°C accuracy. By default, readings are
taken every five minutes and battery life will last over ten years on
the included battery pack.
Power
This Whisker.Block
®
can be powered internally using a 3.7V, 5.2A-H
LiThCl battery pack (10+ years of service life) or 8-24V DC through
Connector 1 pin 1. Select variants are equipped with an internal
5V/18V sensor power supply that can provide up to 30mA to
external sensors; this is available on pin 1 on both connectors when
battery power is used and pin 1 of connector 2 when external DC
power is used.
Range
In an unobstructed, outdoor line-of-site environment, the sensor
should be able to communicate for more than
.5 miles
assuming a
receiving antenna elevation of
10 feet
. If the receiving antenna is
raised to
20 feet
or more, the range should increase to more than
1 mile
. Range performance will degrade if the internal antenna is
used; maximum range is achieved with the external antenna.
Internal Channels
This Whisker.Block
®
is configured with
two (2)
internal channels:
V
DC
Battery Voltage
Ambient Temperature
External Connections
This Whisker.Block
®
is configured with
two (2)
external channels:
4
2
3
1
Not used (Left)
4
2
3
1
Con 1 (Right)
Connector
Pin
Function
Description
1
1
Vin(Vout)
8-24V Input (Sensor Voltage Out)
1
2
Channel 1
Dry Contact
1
3
Channel 2
4-20 mA Analog Input
1
4
Ground
Circuit ground
Ordering Information
Part Number
Description
WB1-9-0D-DCA4NNNN-0000-XR
Dry Contact In, 4-20 mA Analog Input, 900 MHz, 8-24V Ext DC, External Antenna
WB1-9-0D-DCA4NNNN-0000-LR
Dry Contact In, 4-20 mA Analog Input, 900 MHz, 8-24V Ext DC, Internal Antenna
WB1-9-50-DCA4NNNN-0000-XR
Dry Contact In, 4-20 mA Analog Input, 900 MHz, External Antenna
WB1-9-50-DCA4NNNN-0000-LR
Dry Contact In, 4-20 mA Analog Input, 900 MHz, Internal Antenna
WB1-9-10-DCA4NNNN-0000-XR
Dry Contact In, 4-20 mA Analog Input, 900 MHz, External Antenna
WB1-9-10-DCA4NNNN-0000-LR
Dry Contact In, 4-20 mA Analog Input, 900 MHz, Internal Antenna
Wh
sker
o
TM
www.d6labs.com
Page 2
sales@d6labs.com
© Copyright 2026 Digital Six Laboratories, All Right Reserved
1-844-365-8647
Mechanical Drawing - Whisker.Block
®
, Dry Contact & 4-20 mA Analog Input
D6 Labs Whisker.Block Product Diagram
Product Attributes
Type
Description
Series
Whisker.io
®
Features
Dry Contact Input Channel, 4-20 mA Analog Input, M8 Cable Assembly & Internal
(Onboard) Temp
Sensor Type
Dry Contact & Analog Inputs
Battery
3.7V, 5.2A-H LiSOCL
Battery Life Standard Pack
10-20 Years
DC Power
8-24V DC, 100mA max
Operating Temperature Range
-40
-
185°F
Antenna
Internal (LR) / External RPSMA (XR)
Transmission Range
1
1 mile
(typical)
Frequency Range
902-928 MHz
Internal Temperature Measurement Range
-40
-
185°F
Internal Temperature Measurement Accuracy
±
1.8°F
Sensor Sample Rate
5 Minutes(battery power) /10 Seconds(DC power)(typical)
Enclosure
Module - IP67 Case
Packaging
Box
Analog Input Current Range
4-20 mA
1) Typical range: Outdoors, external antenna, line of sight, unobstructed, antenna elevation
40 feet
.